Refresher on Freeze Protection Guidelines for Boilers

Boiler-Blog
Once winter arrives it is a good time to remind our customers about how to properly prepare for freezing temperatures.  This not only applies to when a boiler is in operation, but also when a boiler is down or in transport.  The guidelines below will help get you started, but contact Nationwide Boiler if you have any further questions: 1-800-227-1967.

Freeze Protection Guidelines

Freezing conditions pose a huge risk to boiler equipment if it is not properly protected from the harsh elements. In order to ensure that your unit continues to operate while facing freezing conditions, Nationwide Boiler recommends the following:

  1. Enclose both the front and rear of the boiler area and use an external heat source to minimize freezing conditions.

  2. Install heat tracing with insulation to protect exposed stagnant water lines.

  3. Utilize an appropriate heat tracing method (electric or steam tracing) to all of your main lines and piping components.
      This includes the following lines which should be heat traced regardless if the boiler is in operation or not
      (in freezing conditions): sensing lines (steam drum to CMR, high steam and steam gauge), auxiliary
      low-water-cut-off, water column and level control blowdown. Depending on the length of piping runs,
      the main and continuous blowdown should also be heat traced.

  4. In addition to heat tracing on stagnant sensing lines, drain the lines and fill them with a 50/50 (water/glycol) solution,
      making sure to re-connect the line.

  5. When an extended boiler down time is expected, completely drain the boiler and stagnant water lines.

NOTE: The above lines are considered stagnant lines and should be heat traced regardless if the boiler is in operation or not (freezing conditions).

Nationwide has also done the following in addition to heat tracing on the stagnant sensing lines: 
Drain line, fill with 50/50 (water/glycol) solution, re-connect line. Depending on the length of piping runs, the main and continuous blowdown should also be heat traced. For extended boiler down time, drain boiler and stagnant water lines completely.

  • The above are recommendations; however, use sound engineering judgment calls when there are concerns of possible freeze damage to the equipment. 