Nationwide Boiler is a leading supplier of ultra low NOx solutions for the package boiler industry and beyond. Our CataStak SCR system has been installed in over 200 applications and has been proven to reduce NOx emissions by as much as 99%. We also offer ultra low NOx burner solutions and emissions compliance assistance for California boiler owners facing the most stringent requirements in the country. Contact us today to learn more: 800-227-1966
Check out our common conversions calculator for quick emissions calculations, too!
lbs/MMBtu to ppm (ref. 3% O2, dry) | |||
---|---|---|---|
Natural Gas | Propane | #2 Oil | #6 Oil |
833 | 711 | 780 | 777 |
1368 | 1169 | 1282 | 1277 |
599 | 511 | 561 | 559 |
2394 | 2045 | 2244 | 2235 |
Example: NOx = 0.15 lbs/mmbtu firing natural gas
NOx in ppm = 0.15 x 833 = 125 ppm
lbs/MMBtu to mg/nm3 (ref. 3% O2, dry, 1 atm, 0°C) | ||
---|---|---|
Propane | #2 Oil | #6 Oil |
1676 | 1619 | 1576 |
lbs/MMBtu to mg/nm3 (ref. 3% O2, dry, 1 atm, 0°C) | ||
---|---|---|
Propane | #2 Oil | #6 Oil |
1676 | 1619 | 1576 |
lbs/MMBtu to mg/nm3 (ref. 5% O2, dry, 1 atm, 0°C) | ||
---|---|---|
Propane | #2 Oil | #6 Oil |
1489 | 1442 | 1404 |
lbs/MMBtu to mg/nm3 (ref. 11% O2, dry, 1 atm, 0°C) | ||
---|---|---|
Propane | #2 Oil | #6 Oil |
935 | 887 | 880 |
Example: NOx = 0.15 lbs/mmbtu firing natural gas
NOx = 0.15 x 1704 = 226 mg/nm3 (ref 3% O2, dry, 1 atm, 0C)
Notes: 1. UBHC / VOC conversion based on methane, CH4
2. NG conversions based on analysis: CH4: 95%, C2H6: 5%, N2: 5%
3. #2 Oil conversions based on analysis: C: 87.7%, H: 12.1%, N: 0.02%, S: 0.2%
4. #6 Oil conversions based on analysis: C: 88.2%, H: 10.4%, N: 0.4%, S: 1%
5. Propane conversions based on analysis: C3H8: 100%